Siemens SIMATIC S7-1200 CPU Firmware 4.5.0

CPE Details

Siemens SIMATIC S7-1200 CPU Firmware 4.5.0
4.5.0
2021-08-17
15h05 +00:00
2021-08-20
14h51 +00:00
Alerte pour un CPE
Stay informed of any changes for a specific CPE.
Notifications manage

CPE Name: cpe:2.3:o:siemens:simatic_s7-1200_cpu_firmware:4.5.0:*:*:*:*:*:*:*

Informations

Vendor

siemens

Product

simatic_s7-1200_cpu_firmware

Version

4.5.0

Related CVE

Open and find in CVE List

CVE ID Published Description Score Severity
CVE-2021-37172 2021-08-10 08h35 +00:00 A vulnerability has been identified in SIMATIC S7-1200 CPU family (incl. SIPLUS variants) (V4.5.0). Affected devices fail to authenticate against configured passwords when provisioned using TIA Portal V13. This could allow an attacker using TIA Portal V13 or later versions to bypass authentication and download arbitrary programs to the PLC. The vulnerability does not occur when TIA Portal V13 SP1 or any later version was used to provision the device.
7.5
High