CVE ID | Published | Description | Score | Severity |
---|---|---|---|---|
CWE-924: Improper Enforcement of Message Integrity During Transmission in a Communication Channel vulnerability exists that could cause a denial of service and loss of confidentiality, integrity of controllers when conducting a Man in the Middle attack. | 8.1 |
High |
||
A CWE-754: Improper Check for Unusual or Exceptional Conditions vulnerability exists in the Web Server on Modicon M340, Legacy Offers Modicon Quantum and Modicon Premium and associated Communication Modules (see security notification for affected versions), that could cause denial of HTTP and FTP services when a series of specially crafted requests is sent to the controller over HTTP. | 5.3 |
Medium |
||
A CWE-754: Improper Check for Unusual or Exceptional Conditions vulnerability exists in Modicon M580, Modicon M340, Legacy Controllers Modicon Quantum & Modicon Premium (see security notifications for affected versions), that could cause denial of service when a specially crafted Read Physical Memory request over Modbus is sent to the controller. | 7.5 |
High |
||
A CWE-754: Improper Check for Unusual or Exceptional Conditions vulnerability exists in Modicon M580, Modicon M340, Legacy Controllers Modicon Quantum & Modicon Premium (see security notifications for affected versions), that could cause denial of service when a specially crafted Read Physical Memory request over Modbus is sent to the controller. | 7.5 |
High |
||
A CWE-425: Direct Request ('Forced Browsing') vulnerability exists in the Web Server on Modicon M340, Legacy Offers Modicon Quantum and Modicon Premium and associated Communication Modules (see security notification for affected versions), that could cause disclosure of sensitive data when sending a specially crafted request to the controller over HTTP. | 5.3 |
Medium |
||
A CWE-306: Missing Authentication for Critical Function vulnerability exists in the Web Server on Modicon M340, Legacy Offers Modicon Quantum and Modicon Premium and associated Communication Modules (see security notification for affected versions), that could cause unauthenticated command execution in the controller when sending special HTTP requests. | 9.8 |
Critical |
||
A CWE-754 Improper Check for Unusual or Exceptional Conditions vulnerability exists in the Web Server on Modicon M340, Legacy Offers Modicon Quantum and Modicon Premium and associated Communication Modules (see security notification for affected versions), that could cause a denial of service vulnerability when a specially crafted packet is sent to the controller over HTTP. | 7.5 |
High |
||
A CWE-754: Improper Check for Unusual or Exceptional Conditions vulnerability exists in Modicon M580, Modicon M340, Legacy Controllers Modicon Quantum & Modicon Premium (see security notifications for affected versions), that could cause denial of service when a specially crafted Read Physical Memory request over Modbus is sent to the controller. | 7.5 |
High |
||
A CWE-22: Improper Limitation of a Pathname to a Restricted Directory ('Path Traversal' Vulnerability Type) vulnerability exists in the Web Server on Modicon M340, Legacy Offers Modicon Quantum and Modicon Premium and associated Communication Modules (see security notification for affected versions), that could cause disclosure of information when sending a specially crafted request to the controller over HTTP. | 7.5 |
High |
||
A CWE-754:Improper Check for Unusual or Exceptional Conditions vulnerability exists in Modicon M340 CPUs (BMXP34* versions prior to V3.30) Modicon M340 Communication Ethernet modules (BMXNOE0100 (H) versions prior to V3.4 BMXNOE0110 (H) versions prior to V6.6 BMXNOR0200H all versions), that could cause the device to be unreachable when modifying network parameters over SNMP. | 7.5 |
High |
||
Hard coded accounts exist in Schneider Electric's Modicon Premium, Modicon Quantum, Modicon M340, and BMXNOR0200 controllers in all versions of the communication modules. | 9.8 |
Critical |
||
Vulnerable hash algorithms exists in Schneider Electric's Modicon Premium, Modicon Quantum, Modicon M340, and BMXNOR0200 controllers in all versions of the communication modules. The algorithm used to encrypt the password is vulnerable to hash collision attacks. | 9.8 |
Critical |
||
A buffer overflow vulnerability exists in Schneider Electric's Modicon M340, Modicon Premium, Modicon Quantum PLC, BMXNOR0200. The buffer overflow vulnerability is caused by the length of the source string specified (instead of the buffer size) as the number of bytes to be copied. | 7.5 |
High |
||
An authorization bypass vulnerability exists in Schneider Electric's Modicon M340, Modicon Premium, Modicon Quantum PLC, BMXNOR0200. Requests to CGI functions allow malicious users to bypass authorization. | 9.8 |
Critical |
||
A vulnerability exists in the HTTP request parser in Schneider Electric's Modicon M340, Modicon Premium, Modicon Quantum PLC, BMXNOR0200 which could allow arbitrary code execution. | 9.8 |
Critical |
||
A vulnerability exists in the web services to process SOAP requests in Schneider Electric's Modicon M340, Modicon Premium, Modicon Quantum PLC, BMXNOR0200 which could allow result in a buffer overflow. | 7.5 |
High |