CVE ID | Published | Description | Score | Severity |
---|---|---|---|---|
A CWE-352: Cross-Site Request Forgery (CSRF) vulnerability exists on the web server used, that could cause a leak of sensitive data or unauthorized actions on the web server during the time the user is logged in. Affected Products: Modicon M340 CPUs: BMXP34 (All Versions), Modicon Quantum CPUs with integrated Ethernet (Copro): 140CPU65 (All Versions), Modicon Premium CPUs with integrated Ethernet (Copro): TSXP57 (All Versions), Modicon M340 ethernet modules: (BMXNOC0401, BMXNOE01, BMXNOR0200H) (All Versions), Modicon Quantum and Premium factory cast communication modules: (140NOE77111, 140NOC78*00, TSXETY5103, TSXETY4103) (All Versions) | 8.8 |
High |
||
A CWE-754:Improper Check for Unusual or Exceptional Conditions vulnerability exists in Modicon M340 CPUs (BMXP34* versions prior to V3.30) Modicon M340 Communication Ethernet modules (BMXNOE0100 (H) versions prior to V3.4 BMXNOE0110 (H) versions prior to V6.6 BMXNOR0200H all versions), that could cause the device to be unreachable when modifying network parameters over SNMP. | 7.5 |
High |
||
CWE-284: Improper Access Control vulnerability exists in BMXNOR0200H Ethernet / Serial RTU module (all firmware versions), which could cause the execution of commands by unauthorized users when using IEC 60870-5-104 protocol. | 8.8 |
High |
||
A CWE-754: Improper Check for Unusual or Exceptional Conditions vulnerability exists in BMXNOR0200H Ethernet / Serial RTU module (all firmware versions), which could cause disconnection of active connections when an unusually high number of IEC 60870- 5-104 packets are received by the module on port 2404/TCP. | 8.6 |
High |
||
A Resource Exhaustion issue was discovered in Schneider Electric Modicon M340 PLC BMXNOC0401, BMXNOE0100, BMXNOE0110, BMXNOE0110H, BMXNOR0200H, BMXP341000, BMXP342000, BMXP3420102, BMXP3420102CL, BMXP342020, BMXP342020H, BMXP342030, BMXP3420302, BMXP3420302H, and BMXP342030H. A remote attacker could send a specially crafted set of packets to the PLC causing it to freeze, requiring the operator to physically press the reset button on the PLC in order to recover. | 7.5 |
High |