CVE ID | Published | Description | Score | Severity |
---|---|---|---|---|
Wago web-based management of multiple products has a vulnerability which allows an local authenticated attacker to change the passwords of other non-admin users and thus to escalate non-root privileges. | 5.3 |
Medium |
||
On affected Wago products an remote attacker with administrative privileges can access files to which he has already access to through an undocumented local file inclusion. This access is logged in a different log file than expected. | 2.7 |
Low |
||
In multiple products of WAGO a vulnerability allows an unauthenticated, remote attacker to create new users and change the device configuration which can result in unintended behaviour, Denial of Service and full system compromise. | 9.8 |
Critical |
||
The configuration backend allows an unauthenticated user to write arbitrary data with root privileges to the storage, which could lead to unauthenticated remote code execution and full system compromise. | 9.8 |
Critical |
||
A CORS Misconfiguration in the web-based management allows a malicious third party webserver to misuse all basic information pages on the webserver. In combination with CVE-2022-45138 this could lead to disclosure of device information like CPU diagnostics. As there is just a limited amount of information readable the impact only affects a small subset of confidentiality. | 5.3 |
Medium |
||
The configuration backend of the web-based management can be used by unauthenticated users, although only authenticated users should be able to use the API. The vulnerability allows an unauthenticated attacker to read and set several device parameters that can lead to full compromise of the device. | 9.8 |
Critical |
||
The configuration backend of the web-based management is vulnerable to reflected XSS (Cross-Site Scripting) attacks that targets the users browser. This leads to a limited impact of confidentiality and integrity but no impact of availability. | 6.1 |
Medium |
||
The vulnerability allows a remote unauthenticated attacker to download a backup file, if one exists. That backup file might contain sensitive information like credentials and cryptographic material. A valid user has to create a backup after the last reboot for this attack to be successfull. | 5.9 |
Medium |
||
An exploitable code execution vulnerability exists in the Web-Based Management (WBM) functionality of WAGO PFC 200 03.03.10(15). A specially crafted series of HTTP requests can cause code execution resulting in remote code execution. An attacker can make an authenticated HTTP request to trigger this vulnerability. | 7.2 |
High |
||
An exploitable stack buffer overflow vulnerability vulnerability exists in the iocheckd service "I/O-Check" functionality of WAGO PFC 200. An attacker can send a specially crafted packet to trigger the parsing of this cache file. At 0x1ea28 the extracted state value from the xml file is used as an argument to /etc/config-tools/config_interfaces interface=X1 state= |
7 |
High |
||
An exploitable double free vulnerability exists in the iocheckd service "I/O-Check" functionality of WAGO PFC 200. A specially crafted XML cache file written to a specific location on the device can cause a heap pointer to be freed twice, resulting in a denial of service and potentially code execution. An attacker can send a specially crafted packet to trigger the parsing of this cache file. | 7.8 |
High |
||
An exploitable stack buffer overflow vulnerability vulnerability exists in the iocheckd service "I/O-Check" functionality of WAGO PFC 200. An attacker can send a specially crafted packet to trigger the parsing of this cache file.At 0x1eb9c the extracted interface element name from the xml file is used as an argument to /etc/config-tools/config_interfaces interface= |
7 |
High |
||
An exploitable stack buffer overflow vulnerability vulnerability exists in the iocheckd service ‘I/O-Check’ functionality of WAGO PFC 200 Firmware version 03.02.02(14). A specially crafted XML cache file written to a specific location on the device can cause a stack buffer overflow, resulting in code execution. An attacker can send a specially crafted packet to trigger the parsing of this cache file. The destination buffer sp+0x440 is overflowed with the call to sprintf() for any subnetmask values that are greater than 1024-len(‘/etc/config-tools/config_interfaces interface=X1 state=enabled subnet-mask=‘) in length. A subnetmask value of length 0x3d9 will cause the service to crash. | 7.8 |
High |
||
An exploitable stack buffer overflow vulnerability vulnerability exists in the iocheckd service ‘I/O-Check’ functionality of WAGO PFC 200 Firmware version 03.02.02(14). An attacker can send a specially crafted packet to trigger the parsing of this cache file. The destination buffer sp+0x440 is overflowed with the call to sprintf() for any ip values that are greater than 1024-len(‘/etc/config-tools/config_interfaces interface=X1 state=enabled ip-address=‘) in length. A ip value of length 0x3da will cause the service to crash. | 7.8 |
High |
||
An exploitable stack buffer overflow vulnerability vulnerability exists in the iocheckd service ‘I/O-Check’ functionality of WAGO PFC 200 Firmware version 03.02.02(14). An attacker can send a specially crafted packet to trigger the parsing of this cache file. | 7.8 |
High |
||
An exploitable stack buffer overflow vulnerability vulnerability exists in the iocheckd service ‘I/O-Check’ functionality of WAGO PFC 200 Firmware version 03.02.02(14). An attacker can send a specially crafted packet to trigger the parsing of this cache file. The destination buffer sp+0x440 is overflowed with the call to sprintf() for any hostname values that are greater than 1024-len(‘/etc/config-tools/change_hostname hostname=‘) in length. A hostname value of length 0x3fd will cause the service to crash. | 7.8 |
High |
||
An exploitable stack buffer overflow vulnerability vulnerability exists in the iocheckd service ‘I/O-Check’ functionality of WAGO PFC 200 Firmware version 03.02.02(14). The destination buffer sp+0x440 is overflowed with the call to sprintf() for any domainname values that are greater than 1024-len(‘/etc/config-tools/edit_dns_server domain-name=‘) in length. A domainname value of length 0x3fa will cause the service to crash. | 5.5 |
Medium |
||
An exploitable stack buffer overflow vulnerability vulnerability exists in the iocheckd service ‘I/O-Check’ functionality of WAGO PFC 200 Firmware version 03.02.02(14). An attacker can send a specially crafted packet to trigger the parsing of this cache file.The destination buffer sp+0x40 is overflowed with the call to sprintf() for any gateway values that are greater than 512-len(‘/etc/config-tools/config_default_gateway number=0 state=enabled value=‘) in length. A gateway value of length 0x7e2 will cause the service to crash. | 5.5 |
Medium |
||
An exploitable command injection vulnerability exists in the iocheckd service ‘I/O-Check’ function of the WAGO PFC 200 Firmware version 03.02.02(14). An attacker can send specially crafted packet at 0x1ea48 to the extracted hostname value from the xml file that is used as an argument to /etc/config-tools/config_interfaces interface=X1 state=enabled ip-address= |
7.8 |
High |
||
An exploitable command injection vulnerability exists in the iocheckd service ‘I/O-Check’ function of the WAGO PFC 200 Firmware version 03.02.02(14). A specially crafted XML cache file written to a specific location on the device can be used to inject OS commands. An attacker can send a specially crafted packet to trigger the parsing of this cache file.At 0x1e87c the extracted hostname value from the xml file is used as an argument to /etc/config-tools/change_hostname hostname= |
7.8 |
High |
||
An exploitable command injection vulnerability exists in the iocheckd service ‘I/O-Check’ function of the WAGO PFC 200 Firmware version 03.02.02(14). A specially crafted XML cache file written to a specific location on the device can be used to inject OS commands. An attacker can send a specially crafted packet to trigger the parsing of this cache file. At 0x1e900 the extracted gateway value from the xml file is used as an argument to /etc/config-tools/config_default_gateway number=0 state=enabled value= |
7.8 |
High |
||
An exploitable command injection vulnerability exists in the iocheckd service ‘I/O-Check’ function of the WAGO PFC 200 version 03.02.02(14). A specially crafted XML cache file written to a specific location on the device can be used to inject OS commands. An attacker can send a specially crafted packet to trigger the parsing of this cache file.At 0x1e9fc the extracted subnetmask value from the xml file is used as an argument to /etc/config-tools/config_interfaces interface=X1 state=enabled subnet-mask= |
7.8 |
High |
||
An exploitable command injection vulnerability exists in the iocheckd service ‘I/O-Check’ function of the WAGO PFC 200 Firmware version 03.02.02(14). A specially crafted XML cache file written to a specific location on the device can be used to inject OS commands. An attacker can send a specially crafted packet to trigger the parsing of this cache file.At 0x1ea28 the extracted type value from the xml file is used as an argument to /etc/config-tools/config_interfaces interface=X1 state=enabled config-type= |
7.8 |
High |
||
An exploitable command injection vulnerability exists in the iocheckd service ‘I/O-Check’ function of the WAGO PFC 200 Firmware version 03.02.02(14). An attacker can send a specially crafted packet to trigger the parsing of this cache file. At 0x1e840 the extracted ntp value from the xml file is used as an argument to /etc/config-tools/config_sntp time-server-%d= |
7.8 |
High |
||
An exploitable command injection vulnerability exists in the iocheckd service ‘I/O-Check’ function of the WAGO PFC 200 Firmware version 03.02.02(14). A specially crafted XML cache file written to a specific location on the device can be used to inject OS commands. An attacker can send a specially crafted packet to trigger the parsing of this cache file. At 0x1e9fc the extracted state value from the xml file is used as an argument to /etc/config-tools/config_interfaces interface=X1 state= |
7.8 |
High |
||
An exploitable stack buffer overflow vulnerability vulnerability exists in the iocheckd service ‘I/O-Check’ functionality of WAGO PFC 200 Firmware version 03.02.02(14). An attacker can send a specially crafted packet to trigger the parsing of this cache file.The destination buffer sp+0x440 is overflowed with the call to sprintf() for any type values that are greater than 1024-len(‘/etc/config-tools/config_interfaces interface=X1 state=enabled config-type=‘) in length. A type value of length 0x3d9 will cause the service to crash. | 5.5 |
Medium |
||
An exploitable regular expression without anchors vulnerability exists in the Web-Based Management (WBM) authentication functionality of WAGO PFC200 versions 03.00.39(12) and 03.01.07(13), and WAGO PFC100 version 03.00.39(12). A specially crafted authentication request can bypass regular expression filters, resulting in sensitive information disclosure. | 7.5 |
High |
||
An exploitable remote code execution vulnerability exists in the Cloud Connectivity functionality of WAGO PFC200 versions 03.02.02(14), 03.01.07(13), and 03.00.39(12). A specially crafted XML file will direct the Cloud Connectivity service to download and execute a shell script with root privileges. | 9.1 |
Critical |
||
An exploitable command injection vulnerability exists in the cloud connectivity functionality of WAGO PFC200 versions 03.02.02(14), 03.01.07(13), and 03.00.39(12). An attacker can inject operating system commands into the TimeoutPrepared parameter value contained in the firmware update command. | 7.2 |
High |
||
An exploitable command injection vulnerability exists in the Cloud Connectivity functionality of WAGO PFC200 Firmware versions 03.02.02(14), 03.01.07(13), and 03.00.39(12). An attacker can inject OS commands into the TimeoutUnconfirmed parameter value contained in the Firmware Update command. | 7.2 |
High |
||
An exploitable improper host validation vulnerability exists in the Cloud Connectivity functionality of WAGO PFC200 Firmware versions 03.02.02(14), 03.01.07(13), and 03.00.39(12). A specially crafted HTTPS POST request can cause the software to connect to an unauthorized host, resulting in unauthorized access to firmware update functionality. An attacker can send an authenticated HTTPS POST request to direct the Cloud Connectivity software to connect to an attacker controlled Azure IoT Hub node. | 9.1 |
Critical |
||
An exploitable command injection vulnerability exists in the iocheckd service ‘I/O-Check’ function of the WAGO PFC 200 version 03.02.02(14). An attacker can send a specially crafted XML cache file At 0x1e8a8 the extracted domainname value from the xml file is used as an argument to /etc/config-tools/edit_dns_server domain-name= |
7.8 |
High |
||
An exploitable stack buffer overflow vulnerability exists in the iocheckd service ‘I/O-Check’ functionality of WAGO PFC 200 version 03.02.02(14). A specially crafted XML cache file written to a specific location on the device can cause a stack buffer overflow, resulting in code execution. An attacker can send a specially crafted packet to trigger the parsing of this cache file. | 7.8 |
High |
||
An exploitable timing discrepancy vulnerability exists in the authentication functionality of the Web-Based Management (WBM) web application on WAGO PFC100/200 controllers. The WBM application makes use of the PHP crypt() function which can be exploited to disclose hashed user credentials. This affects WAGO PFC200 Firmware version 03.00.39(12) and version 03.01.07(13), and WAGO PFC100 Firmware version 03.00.39(12). | 5.3 |
Medium |
||
The WBM web application on firmwares prior to 03.02.02 and 03.01.07 on the WAGO PFC100 and PFC2000, respectively, runs on a lighttpd web server and makes use of the FastCGI module, which is intended to provide high performance for all Internet applications without the penalties of Web server APIs. However, the default configuration of this module appears to limit the number of concurrent php-cgi processes to two, which can be abused to cause a denial of service of the entire web server. This affects WAGO PFC200 Firmware version 03.00.39(12) and version 03.01.07(13), and WAGO PFC100 Firmware version 03.00.39(12) and version 03.02.02(14). | 7.5 |
High |
||
An exploitable command injection vulnerability exists in the cloud connectivity feature of WAGO PFC200. An attacker can inject operating system commands into any of the parameter values contained in the firmware update command. This affects WAGO PFC200 Firmware version 03.02.02(14), version 03.01.07(13), and version 03.00.39(12) | 7.2 |
High |
||
eap.c in pppd in ppp 2.4.2 through 2.4.8 has an rhostname buffer overflow in the eap_request and eap_response functions. | 9.8 |
Critical |
||
An exploitable heap buffer overflow vulnerability exists in the iocheckd service I/O-Check functionality of WAGO PFC200 Firmware version 03.01.07(13), WAGO PFC200 Firmware version 03.00.39(12), and WAGO PFC100 Firmware version 03.00.39(12). A specially crafted set of packets can cause a heap buffer overflow, potentially resulting in code execution. An attacker can send unauthenticated packets to trigger this vulnerability. | 9.8 |
Critical |
||
Information Disclosure is possible on WAGO Series PFC100 and PFC200 devices before FW12 due to improper access control. A remote attacker can check for the existence of paths and file names via crafted HTTP requests. | 5.3 |
Medium |
||
An Improper Authentication issue was discovered in WAGO PFC200 Series 3S CoDeSys Runtime versions 2.3.X and 2.4.X. An attacker can execute different unauthenticated remote operations because of the CoDeSys Runtime application, which is available via network by default on Port 2455. An attacker could execute some unauthenticated commands such as reading, writing, or deleting arbitrary files, or manipulate the PLC application during runtime by sending specially-crafted TCP packets to Port 2455. | 9.8 |
Critical |
||
An issue was discovered in WAGO 750-8202/PFC200 prior to FW04 (released August 2015), WAGO 750-881 prior to FW09 (released August 2016), and WAGO 0758-0874-0000-0111. By accessing a specific uniform resource locator (URL) on the web server, a malicious user is able to edit and to view settings without authenticating. | 9.1 |
Critical |