Siemens SIMATIC S7-1200

CPE Details

Siemens SIMATIC S7-1200
-
2017-05-22 23:51 +00:00
2021-05-14 15:51 +00:00

Alerte pour un CPE

Stay informed of any changes for a specific CPE.
Alert management

CPE Name: cpe:2.3:h:siemens:simatic_s7-1200:-:*:*:*:*:*:*:*

Informations

Vendor

siemens

Product

simatic_s7-1200

Version

-

Related CVE

Open and find in CVE List

CVE ID Published Description Score Severity
CVE-2012-3037 2022-10-03 14:15 +00:00 The Siemens SIMATIC S7-1200 2.x PLC does not properly protect the private key of the SIMATIC CONTROLLER Certification Authority certificate, which allows remote attackers to spoof the S7-1200 web server by using this key to create a forged certificate.
4.3
CVE-2020-28400 2021-07-13 09:02 +00:00 Affected devices contain a vulnerability that allows an unauthenticated attacker to trigger a denial-of-service condition. The vulnerability can be triggered if a large amount of DCP reset packets are sent to the device.
7.5
HIGH
CVE-2019-13945 2019-12-12 12:19 +00:00 A vulnerability has been identified in SIMATIC S7-1200 CPU family (incl. SIPLUS variants) (All versions), SIMATIC S7-1200 CPU family < V4.x (incl. SIPLUS variants) (All versions), SIMATIC S7-1200 CPU family V4.x (incl. SIPLUS variants) (All versions with Function State (FS) < 11), SIMATIC S7-200 SMART CPU CR20s (6ES7 288-1CR20-0AA1) (All versions <= V2.3.0 and Function State (FS) <= 3), SIMATIC S7-200 SMART CPU CR30s (6ES7 288-1CR30-0AA1) (All versions <= V2.3.0 and Function State (FS) <= 3), SIMATIC S7-200 SMART CPU CR40 (6ES7 288-1CR40-0AA0) (All versions <= V2.2.2 and Function State (FS) <= 8), SIMATIC S7-200 SMART CPU CR40s (6ES7 288-1CR40-0AA1) (All versions <= V2.3.0 and Function State (FS) <= 3), SIMATIC S7-200 SMART CPU CR60 (6ES7 288-1CR60-0AA0) (All versions <= V2.2.2 and Function State (FS) <= 10), SIMATIC S7-200 SMART CPU CR60s (6ES7 288-1CR60-0AA1) (All versions <= V2.3.0 and Function State (FS) <= 3), SIMATIC S7-200 SMART CPU SR20 (6ES7 288-1SR20-0AA0) (All versions <= V2.5.0 and Function State (FS) <= 11), SIMATIC S7-200 SMART CPU SR30 (6ES7 288-1SR30-0AA0) (All versions <= V2.5.0 and Function State (FS) <= 10), SIMATIC S7-200 SMART CPU SR40 (6ES7 288-1SR40-0AA0) (All versions <= V2.5.0 and Function State (FS) <= 10), SIMATIC S7-200 SMART CPU SR60 (6ES7 288-1SR60-0AA0) (All versions <= V2.5.0 and Function State (FS) <= 12), SIMATIC S7-200 SMART CPU ST20 (6ES7 288-1ST20-0AA0) (All versions <= V2.5.0 and Function State (FS) <= 9), SIMATIC S7-200 SMART CPU ST30 (6ES7 288-1ST30-0AA0) (All versions <= V2.5.0 and Function State (FS) <= 9), SIMATIC S7-200 SMART CPU ST40 (6ES7 288-1ST40-0AA0) (All versions <= V2.5.0 and Function State (FS) <= 8), SIMATIC S7-200 SMART CPU ST60 (6ES7 288-1ST60-0AA0) (All versions <= V2.5.0 and Function State (FS) <= 8), SIMATIC S7-200 SMART CPU family (All versions). There is an access mode used during manufacturing of the affected devices that allows additional diagnostic functionality. The security vulnerability could be exploited by an attacker with physical access to the UART interface during boot process.
6.8
MEDIUM
CVE-2018-13815 2018-12-13 15:00 +00:00 A vulnerability has been identified in SIMATIC S7-1200 (All versions), SIMATIC S7-1500 (All Versions < V2.6). An attacker could exhaust the available connection pool of an affected device by opening a sufficient number of connections to the device. Successful exploitation requires an attacker to be able to send packets to port 102/tcp of the affected device. No user interaction and no user privileges are required to exploit the vulnerability. The vulnerability, if exploited, could cause a Denial-of-Service condition impacting the availability of the system. At the time of advisory publication no public exploitation of this vulnerability was known.
7.5
HIGH
CVE-2017-12741 2017-12-26 03:00 +00:00 A vulnerability has been identified in Development/Evaluation Kits for PROFINET IO: DK Standard Ethernet Controller, Development/Evaluation Kits for PROFINET IO: EK-ERTEC 200, Development/Evaluation Kits for PROFINET IO: EK-ERTEC 200P, SIMATIC Compact Field Unit, SIMATIC ET200AL, SIMATIC ET200M (incl. SIPLUS variants), SIMATIC ET200MP IM155-5 PN BA (incl. SIPLUS variants), SIMATIC ET200MP IM155-5 PN HF (incl. SIPLUS variants), SIMATIC ET200MP IM155-5 PN ST (incl. SIPLUS variants), SIMATIC ET200S (incl. SIPLUS variants), SIMATIC ET200SP IM155-6 PN BA (incl. SIPLUS variants), SIMATIC ET200SP IM155-6 PN HA (incl. SIPLUS variants), SIMATIC ET200SP IM155-6 PN HF (incl. SIPLUS variants), SIMATIC ET200SP IM155-6 PN HS (incl. SIPLUS variants), SIMATIC ET200SP IM155-6 PN ST (incl. SIPLUS variants), SIMATIC ET200ecoPN, 16DI, DC24V, 8xM12, SIMATIC ET200ecoPN, 16DO DC24V/1,3A, 8xM12, SIMATIC ET200ecoPN, 4AO U/I 4xM12, SIMATIC ET200ecoPN, 8 DIO, DC24V/1,3A, 8xM12, SIMATIC ET200ecoPN, 8 DO, DC24V/2A, 8xM12, SIMATIC ET200ecoPN, 8AI RTD/TC 8xM12, SIMATIC ET200ecoPN, 8AI; 4 U/I; 4 RTD/TC 8xM12, SIMATIC ET200ecoPN, 8DI, DC24V, 4xM12, SIMATIC ET200ecoPN, 8DI, DC24V, 8xM12, SIMATIC ET200ecoPN, 8DO, DC24V/0,5A, 4xM12, SIMATIC ET200ecoPN, 8DO, DC24V/1,3A, 4xM12, SIMATIC ET200ecoPN, 8DO, DC24V/1,3A, 8xM12, SIMATIC ET200ecoPN: IO-Link Master, SIMATIC ET200pro, SIMATIC PN/PN Coupler (incl. SIPLUS NET variants), SIMATIC S7-1200 CPU family (incl. SIPLUS variants), SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants), SIMATIC S7-1500 Software Controller, SIMATIC S7-200 SMART, SIMATIC S7-300 CPU family (incl. related ET200 CPUs and SIPLUS variants), SIMATIC S7-400 H V6 CPU family and below (incl. SIPLUS variants), SIMATIC S7-400 PN/DP V6 CPU family and below (incl. SIPLUS variants), SIMATIC S7-400 PN/DP V7 CPU family (incl. SIPLUS variants), SIMATIC S7-410 V8 CPU family (incl. SIPLUS variants), SIMATIC TDC CP51M1, SIMATIC TDC CPU555, SIMATIC WinAC RTX (F) 2010, SIMOCODE pro V EIP (incl. SIPLUS variants), SIMOCODE pro V PN (incl. SIPLUS variants), SIMOTION C, SIMOTION D (incl. SIPLUS variants), SIMOTION D4xx V4.4 for SINAMICS SM150i-2 w. PROFINET (incl. SIPLUS variants), SIMOTION P V4.4 and V4.5, SIMOTION P V5, SINAMICS DCM w. PN, SINAMICS DCP w. PN, SINAMICS G110M w. PN, SINAMICS G120(C/P/D) w. PN (incl. SIPLUS variants), SINAMICS G130 V4.7 w. PN, SINAMICS G130 V4.8 w. PN, SINAMICS G150 V4.7 w. PN, SINAMICS G150 V4.8 w. PN, SINAMICS GH150 V4.7 w. PROFINET, SINAMICS GL150 V4.7 w. PROFINET, SINAMICS GM150 V4.7 w. PROFINET, SINAMICS S110 w. PN, SINAMICS S120 V4.7 SP1 w. PN (incl. SIPLUS variants), SINAMICS S120 V4.7 w. PN (incl. SIPLUS variants), SINAMICS S120 V4.8 w. PN (incl. SIPLUS variants), SINAMICS S120 prior to V4.7 w. PN (incl. SIPLUS variants), SINAMICS S150 V4.7 w. PN, SINAMICS S150 V4.8 w. PN, SINAMICS SL150 V4.7.0 w. PROFINET, SINAMICS SL150 V4.7.4 w. PROFINET, SINAMICS SL150 V4.7.5 w. PROFINET, SINAMICS SM120 V4.7 w. PROFINET, SINAMICS V90 w. PN, SINUMERIK 840D sl, SIRIUS Soft Starter 3RW44 PN. Specially crafted packets sent to port 161/udp could cause a Denial-of-Service condition. The affected devices must be restarted manually.
7.5
HIGH
CVE-2017-2681 2017-05-11 08:00 +00:00 Specially crafted PROFINET DCP packets sent on a local Ethernet segment (Layer 2) to an affected product could cause a denial of service condition of that product. Human interaction is required to recover the system. PROFIBUS interfaces are not affected. This vulnerability affects only SIMATIC HMI Multi Panels and HMI Mobile Panels, and S7-300/S7-400 devices.
6.5
MEDIUM
CVE-2017-2680 2017-05-10 23:00 +00:00 Specially crafted PROFINET DCP broadcast packets could cause a denial of service condition of affected products on a local Ethernet segment (Layer 2). Human interaction is required to recover the systems. PROFIBUS interfaces are not affected.
6.5
MEDIUM
CVE-2013-0700 2013-04-21 23:00 +00:00 Siemens SIMATIC S7-1200 PLCs 2.x and 3.x allow remote attackers to cause a denial of service (defect-mode transition and control outage) via crafted packets to TCP port 102 (aka the ISO-TSAP port).
7.8
CVE-2013-2780 2013-04-21 23:00 +00:00 Siemens SIMATIC S7-1200 PLCs 2.x and 3.x allow remote attackers to cause a denial of service (defect-mode transition and control outage) via crafted packets to UDP port 161 (aka the SNMP port).
7.8
CVE-2012-3040 2012-10-10 16:00 +00:00 Cross-site scripting (XSS) vulnerability in the web server on Siemens SIMATIC S7-1200 PLCs 2.x through 3.0.1 allows remote attackers to inject arbitrary web script or HTML via a crafted URI.
4.3