Siemens SIMATIC S7-1200 Firmware -

CPE Details

Siemens SIMATIC S7-1200 Firmware -
-
2017-05-22
23h51 +00:00
2021-05-26
13h05 +00:00
Alerte pour un CPE
Stay informed of any changes for a specific CPE.
Notifications manage

CPE Name: cpe:2.3:o:siemens:simatic_s7-1200_firmware:-:*:*:*:*:*:*:*

Informations

Vendor

siemens

Product

simatic_s7-1200_firmware

Version

-

Related CVE

Open and find in CVE List

CVE ID Published Description Score Severity
CVE-2020-28400 2021-07-13 09h02 +00:00 Affected devices contain a vulnerability that allows an unauthenticated attacker to trigger a denial of service condition. The vulnerability can be triggered if a large amount of DCP reset packets are sent to the device.
8.7
High
CVE-2019-13945 2019-12-12 12h19 +00:00 A vulnerability has been identified in SIMATIC S7-1200 CPU family (incl. SIPLUS variants) (All versions), SIMATIC S7-1200 CPU family < V4.x (incl. SIPLUS variants) (All versions), SIMATIC S7-1200 CPU family V4.x (incl. SIPLUS variants) (All versions with Function State (FS) < 11), SIMATIC S7-200 SMART CPU CR20s (6ES7 288-1CR20-0AA1) (All versions <= V2.3.0 and Function State (FS) <= 3), SIMATIC S7-200 SMART CPU CR30s (6ES7 288-1CR30-0AA1) (All versions <= V2.3.0 and Function State (FS) <= 3), SIMATIC S7-200 SMART CPU CR40 (6ES7 288-1CR40-0AA0) (All versions <= V2.2.2 and Function State (FS) <= 8), SIMATIC S7-200 SMART CPU CR40s (6ES7 288-1CR40-0AA1) (All versions <= V2.3.0 and Function State (FS) <= 3), SIMATIC S7-200 SMART CPU CR60 (6ES7 288-1CR60-0AA0) (All versions <= V2.2.2 and Function State (FS) <= 10), SIMATIC S7-200 SMART CPU CR60s (6ES7 288-1CR60-0AA1) (All versions <= V2.3.0 and Function State (FS) <= 3), SIMATIC S7-200 SMART CPU SR20 (6ES7 288-1SR20-0AA0) (All versions <= V2.5.0 and Function State (FS) <= 11), SIMATIC S7-200 SMART CPU SR30 (6ES7 288-1SR30-0AA0) (All versions <= V2.5.0 and Function State (FS) <= 10), SIMATIC S7-200 SMART CPU SR40 (6ES7 288-1SR40-0AA0) (All versions <= V2.5.0 and Function State (FS) <= 10), SIMATIC S7-200 SMART CPU SR60 (6ES7 288-1SR60-0AA0) (All versions <= V2.5.0 and Function State (FS) <= 12), SIMATIC S7-200 SMART CPU ST20 (6ES7 288-1ST20-0AA0) (All versions <= V2.5.0 and Function State (FS) <= 9), SIMATIC S7-200 SMART CPU ST30 (6ES7 288-1ST30-0AA0) (All versions <= V2.5.0 and Function State (FS) <= 9), SIMATIC S7-200 SMART CPU ST40 (6ES7 288-1ST40-0AA0) (All versions <= V2.5.0 and Function State (FS) <= 8), SIMATIC S7-200 SMART CPU ST60 (6ES7 288-1ST60-0AA0) (All versions <= V2.5.0 and Function State (FS) <= 8), SIMATIC S7-200 SMART CPU family (All versions). There is an access mode used during manufacturing of the affected devices that allows additional diagnostic functionality. The security vulnerability could be exploited by an attacker with physical access to the UART interface during boot process.
6.8
Medium
CVE-2018-13815 2018-12-13 15h00 +00:00 A vulnerability has been identified in SIMATIC S7-1200 (All versions), SIMATIC S7-1500 (All Versions < V2.6). An attacker could exhaust the available connection pool of an affected device by opening a sufficient number of connections to the device. Successful exploitation requires an attacker to be able to send packets to port 102/tcp of the affected device. No user interaction and no user privileges are required to exploit the vulnerability. The vulnerability, if exploited, could cause a Denial-of-Service condition impacting the availability of the system. At the time of advisory publication no public exploitation of this vulnerability was known.
7.5
High
CVE-2017-12741 2017-12-26 03h00 +00:00 Specially crafted packets sent to port 161/udp could cause a denial of service condition. The affected devices must be restarted manually.
8.7
High
CVE-2017-2681 2017-05-11 08h00 +00:00 Specially crafted PROFINET DCP packets sent on a local Ethernet segment (Layer 2) to an affected product could cause a denial of service condition of that product. Human interaction is required to recover the system. PROFIBUS interfaces are not affected.
7.1
High
CVE-2017-2680 2017-05-10 23h00 +00:00 Specially crafted PROFINET DCP broadcast packets could cause a denial of service condition of affected products on a local Ethernet segment (Layer 2). Human interaction is required to recover the systems. PROFIBUS interfaces are not affected.
7.1
High
CVE-2013-0700 2013-04-21 23h00 +00:00 Siemens SIMATIC S7-1200 PLCs 2.x and 3.x allow remote attackers to cause a denial of service (defect-mode transition and control outage) via crafted packets to TCP port 102 (aka the ISO-TSAP port).
7.8
CVE-2013-2780 2013-04-21 23h00 +00:00 Siemens SIMATIC S7-1200 PLCs 2.x and 3.x allow remote attackers to cause a denial of service (defect-mode transition and control outage) via crafted packets to UDP port 161 (aka the SNMP port).
7.8